Liquid Level Sensing The LL F/D/A/O/C senses conductive non hazardous fluids with low voltage contact probes.

Internal logic circuitry controls the relay latching for tank Fill or Drain operations. Three diagnostic LEDs indicate the input and output relay states.

The sensitivity is adjustable to control effects of liquid wickers from the level probes.

The Alarm version operates as a Dual High and Low Level Alarm or it may be operated as either a High or Low Alarm. A delay timer reduces wave effects.

Pin 6 is NO input & pin 8 is NC input

Specifications

Input Supply Voltage

  • 12 or 24 Vac, 20 %
  • 120 or 240 Vac, 20 %

Frequency

  • 50/60 Hz

Power Consumption

  • 2 VA

Sensitivity Range

  • 5K to 100KO

Pick-Up & Drop-Out Delays

  • 5 Sec. Fixed

Maximum Probe Voltage (AC)

  • 16 V

Output Rating at 25° C

  • 5 A @ 250 Vac
  • 10 A @ 120 Vac
  • 30 Vdc 300W (D.C.)
  • 1600 VA (A.C.) Max. switching power (resistive)
  • 100,000 Full Load Electrical Cycles
  • 20,000,000 Mechanical Cycles

Indicators

  • 1 Relay Status LED
  • 2 Input Status LEDs: Closed Connection On

Mounting

  • Plug-In

Termination

  • 8-pin (Octal)

Packaging

  • Dust Cover

Weight

  • 9 oz.

Ambient Operating Temperature

  • 0° to 40° C

Ambient Storage Temperature

  • -40° to 85° C

Certifications

  • UL E71902 Standard

  • Duplex Pumping
  • Lift Stations
  • Pumps or Compressors
  • Level Sensing (Float or Probe)
  • Combustible or Hazardous Locations
  • Simplex Pumping