Features
  • Smoke dampers are designed for operation in temperatures ranging between -40°F (-40°C) and 250°F (121°C).
  • UL/ULC rated Leakage Class 1. This is the best possible leakage class attainable.
  • Approved for use with Belimo or Honeywell acutators with 24, 120, or 230 vac, single phase, two-position control.
  • AMCA certified for pressure drop.
  • Aluminum extrusions contribute to a prolonged and rust-free operational life.
  • Bearings are composed of a 2 part (inner and outer) bronze oilite bearing system, fixed to an aluminum hexagon blade pivot pin. This system prevents bearings from rotating directly within the frame and around the axle.
  • These dampers are supplied with extremely flexible silicone seals that are resistant to weathering, compression set, and heat, thus ensuring consistent minimal leakage rate performance and sealing longevity.
  • Standard blade depth is 6” (152 mm).

Specifications

Leakage Rating

  • Class 1

Operational Rating

  • Airflow: 2000 fpm (10.2 m/s). Rated for airflow in either direction
  • Temperature: 250° F (121° C)
  • Pressure: 4" w.g. (1 kPa) static pressure differential

Fail Position

  • Closed

Maximum Single-Section Opening Size

  • 36"w x 48"h (915 mm x 1220 mm)

Maximum multi-Section Opening Sizes

  • 144"w x 96"h (3658 mm x 2438 mm)
  • 288"w x 48"h (7316 mm x 1220 mm)

Minimum Section Size

  • 11"w x 8.25"h (280 mm x 210 mm)

Maximum Section Size

  • 12 ft² (1.1 m²)
  • 36"w x 48"h (915 mm x 1220 mm)