Web.Requests
Yodify DEC Brand Library
GTx116e-P+ Airflow Measurement with Temperature and Alarm Capability

GTx116e-P+ Airflow Measurement with Temperature and Alarm Capability

Brand: EBTRON, Inc

The GTx116e‐P+ is EBTRON’s top‐of‐the‐line solution for accurate and repeatable measurement in ducts and plenums. Ideal for outdoor air delivery monitoring and airflow tracking applications. 

Temperature and alarm capability plus unsurpassed product features and connectivity options make this the best choice for today’s high performance buildings. 

Bluetooth® low energy technology interface.
Features
  • Thermal Dispersion Airflow Technology
  • Supports up to 16 Sensor Nodes
  • NIST-traceable Calibration
  • %-of-reading Airflow Accuracy
  • Airflow and Status Alarms
  • Temperature Output Capability
  • Combination Analog/Network Models
  • Three Mounting Styles
  • Remote Transmitter with LCD Display
  • 3-year Warranty

1 - 1 of 1 Part Numbers
GTx116e-P+
GTx116e-P+
EBTRON Airflow Measurement with Temperature and Alarm Capability
The GTx116e‐P+ is EBTRON’s top‐of‐the‐line solution for accurate and repeatable measurement in ducts and plenums. Ideal for outdoor air delivery monitoring and airflow tracking applications. 

Temperature and alarm capability plus unsurpassed product features and connectivity options make this the best choice for today’s high performance buildings. Bluetooth® low energy technology interface.
1 - 1 of 1 Part Numbers

Specifications

Probe and Sensor Node Configurations (Maximum)

  • 2 Probes x 8 Sensor Nodes/Probe
  • 4 Probes x 4 Sensor Nodes/Probe

Certifications & Approvals

  • BTL
  • FCC
  • RoHS
  • CE
  • cULus Listed

NIST

  • NIST-traceable Calibration

Temperature Range

  • Transmitter: -20° to 120° F (-28.9° to 48.9° C)
  • Probe: -20° to 160° F (-28.9° to 71.1° C)

Humidity

  • Transmitter: 5 to 95 % Non-Condensing
  • Probes: 0 to 100 % Non-Condensing

Installed Airflow Accuracy

  • Non-ducted OA Intakes: Better than or Equal to ± 5 % of Reading
  • Ducts/Plenums: ± 3 % of Reading

Measured Accuracy

  • Temperature: ± 0.15° F (0.08° C) to NIST-traceable Temperature Standards
  • Airflow: ± 2 % of Reading to NIST-traceable Airflow Standards

Material of Construction

  • Mounting Bracket: 304 Stainless Steel
  • Sensor Probe Tube: Gold Anodized 6063 Aluminum, 316 Stainless Steel with/ Stainless Steel Option)

Power Requirement

  • Transmitter: 24 Vac (22.8-26.4 Under Load) @ 20 V-A Max.

Alarm

  • Airflow: Low and/or High User Defined Set Point Alarm
  • System Status Alarm: Sensor Diagnostic System Trouble Indication

  • Outdoor Air Delivery  Monitoring
  • Differential Airflow Tracking
  • Hospital Pressurization
  • Laboratory Pressurization
  • Air Change Verification &  Monitoring
  • System Performance  Monitoring
Brand-Managed Distributed Enterprise Catalogs (DEC)
for Authorized Channel Partners
Book a DEC Demo